SWITCHING SELECTION OF ADDRESS SETTING MODE
4) To activate the address setting mode, hold down the three buttons of SET TEMP. V, SET
TEMP. Λ and FAN at the same time for 5 seconds or longer.
Address setting mode initial display
BUTTON NAME AND FUNCTION
Refer to “1-2” for an outline of the address setting. ●
It does not matter whether the refrigerant circuit address or indoor unit address is set first. ●
(The method shown here sets the indoor unit address first.)
During address setting mode, indoor unit reject the any operation command from remote controller. ●
Function number
01---Indoor unit address
02---Refrigerant circuit address
Remote controller address
Remote controller address
setting number 00-15
SET BACK button
Switches the remote controller
address setting number.
SET TIME “<” and “>” button
Switches the function number.
Setting number
Setting number
Indoor unit address valid range 00-63 ●
Refrigerant circuit address valid range ●
00-99
SET TEMP. “V” and “
Λ
” button
Switches the setting number.
TIMER SET button
Transmits address setting
- (07-26) -