COMPLETION OF ADDRESS SETTING MODE
13) Press the three buttons of SET TEMP.
p
, SET TEMP.
q
and FAN at the same time for 5
seconds or longer. The address setting mode will be cleared and the normal mode display
will be restored.
Normal mode display
If no key entry is made for 60 seconds, even though none of the above buttons is
¾
pressed, the address setting mode will automatically be cleared.
(If the address setting mode is automatically cleared while setting addresses,
activate the mode again according to the procedure in step 4) above.)
SETTING UP EACH INDOOR UNIT
0001 0101 0201 1301 1401 15010 1 2 0 1 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Repeat the procedures in steps 1) through 13), and set up the indoor units
requiring address setting.
Simple remote
controller
Simple remote
controller
Simple remote
controller
RESET THE POWER AFTER SETTING UP ADDRESS OF ALL
INDOOR UNITS
Important
If the reset is not performed, address can not be read in normally.
¾
After all the addresses have been set, the circuit breaker needs to be switched off
¾
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set address is stored in the PCB and will remain in memory even when the
¾
power is turned off.
However setting address is effective after power reset.
Record the address set in the indoor unit on a label, etc., and afx the label to the
unit so it can be used for after-sales service operations.
- (07-34) -
FUNCTION
SETTING
FUNCTION
SETTING