z
If indoor unit whose cooling capacity is 1.1 kW is connected, calculate the value according to the following restric-
tions.
Maximum volume ratio of indoor units.
1.1 kW cooling capacity
indoor unit is NOT
connected
1.1 kW cooling capacity indoor unit is connected
9.0 kW or larger cooling capacity
AU or AR is NOT connected
9.0 kW or larger cooling capacity
AU or AR is connected
130%
120% (J-II) *1
117% (J-IIS) *1
110% (J-II and J-IIS) *1
*1: Keep the volume ratio within the specied value above.
When 1.1 kW cooling capacity indoor unit is connected, "PASS" is displayed if the volume ratio is 130 % or
less, even if it is over 110 % or 120 %.
If the estimated volume ratio is over specied value mentioned above, reconsider the connecting capacity of
the indoor units.
- (07-59) -