V-III series2-1-2.
SETTINGS LIST
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
0 0
Pipe length
setting
0 0 Standard (40 to 65m)
l
¡
-
*1
Pipe length means the length
between master outdoor unit
and the nearest indoor unit.
0 1 Short (less than 40m)
0 2 Medium (65 to 90m)
0 3 Long 1 (90 to 120m)
0 4 Long 2 (120 to 165m)
1 0
Sequential start
shift
0 0 Normal
l
¡
-
*1
The start-up timing of outdoor
unit (compressor) can be set
up so that it can delay several
seconds.
This feature is useful when
multiple number of outdoor units
are installed and turned on at
the same time
to limit the starting current.
0 1 21sec. Delay
0 2 42sec. Delay
0 3 63sec. Delay
1 1
Cooling
capacity shift
0 0 Normal mode
l
¡
-
*1
0 1 Save energy mode 1
0 2 High power mode 1
0 3 High power mode 2
0 4 Prohibited
1 2
Heating
capacity shift
0 0 Normal mode
l
¡
-
*1
0 1 Save energy mode
0 2 High power mode 1
0 3 High power mode 2
1 3 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
1 7
Height
difference
between indoor
units
0 0 Standard
l
¡
-
*1
If installing the indoor units (even
only one set) to a lower oor
than the outdoor unit, and the
height difference between the
indoor units is 3m or greater (i.e.,
if installing the indoor units on
separate oors), set "02 (height
difference)".
0 1 Prohibited
0 2 Height difference
0 3 Prohibited
0 4 Prohibited
*1: Do not set this for outdoor units with Slave setting.
- (07-68) -
FUNCTION
SETTING
FUNCTION
SETTING