LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
3 0
Energy saving
level setting
0 0 Level 1 (stop)
l
¡
-
*1
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the “Energy
Saving Peak Cut function.
The lower the level, the more
the effect of energy saving, but
the cooling/heating performance
will also drop.
0 1
Level 2 (operated at
40% capacity)
0 2
Level 3 (operated at
60% capacity)
0 3
Level 4 (operated at
80% capacity)
0 4
Level 5 (operated at
100% capacity)
4 0
Capacity
priority setting
(in low noise
mode)
0 0 Off (quiet priority)
l
¡
-
*1
If the cooling/heating
performance becomes
insufcient when the low noise
mode is set, it is possible to
set “capacity priority” that
automatically cancels the low
noise mode (once performance
is restored, the mode will
automatically return to the low
noise mode).
0 1 On (capacity priority)
4 1
Low noise
mode setting
0 0 Off (Normal)
l
¡
-
*1
0 1 On (Low noise mode)
4 2
Low noise
mode
operation level
setting
0 0 Level 1 (55dB)
l
¡
-
*1
The noise level when operating
in the low noise mode can be
set.
0 1 Level 2 (50dB)
6 0
Recovery
operation
0 0 On
l
¡
-
*1
0 1 Off
*1: Do not set this for outdoor units with Slave setting.
- (07-75) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents