LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Remarks
3 0
Outdoor unit
capacity save
setting
0 0 Level 1 (stop)
l
The capacity limit can be selected by the
external input terminal (CN133) when operating
with the “Outdoor unit capacity save function.”
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance will also drop.
0 1 Level 2
0 2 Level 3
0 3 Level 4
0 4 Level 5
3 1 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
4 0
Capacity
priority setting
(in low noise
mode)
0 0 Off (quiet priority)
l
If the cooling/heating performance becomes
insufcient when the low noise mode is set,
it is possible to set “capacity priority” that
automatically cancels the low noise mode
(once performance is restored, the mode will
automatically return to the low noise mode).
0 1 On (capacity priority)
4 1
Low noise
mode setting
0 0 Off (Normal)
l
0 1 On (Low noise mode)
4 2 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
6 0 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
- (07-79) -
FUNCTION
SETTING
FUNCTION
SETTING