EasyManua.ls Logo

Fujitsu Airstage J-II - Page 635

Fujitsu Airstage J-II
836 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COMPLETION OF FUNCTION SETTING MODE
8) Press the three buttons of SET TEMP.
p
, SET TEMP.
q
and FAN at the same time for 5
seconds or longer. The function setting mode will be cleared and the regular display will
be restored.
Normal mode display
If no key entry is made for 60 seconds, even though none of the above buttons is
¾
pressed, the function setting mode will automatically be cleared.
(If the function setting mode is automatically cleared while setting addresses,
activate the mode again according to the procedure in step 3) above.)
SETTING UP EACH INDOOR UNIT
0001 0101 0201 1301 1401 15010 1 2 0 1 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Repeat the procedures in steps 1) through 8), and set up the indoor units
requiring function setting.
Simple remote
controller
Simple remote
controller
Simple remote
controller
RESET THE POWER AFTER SETTING UP FUNCTION OF ALL
INDOOR UNITS
Important
If the reset is not performed, function can not be read in normally.
¾
After all the functions have been set, the circuit breaker needs to be switched off
¾
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set function is stored in the PCB and will remain in memory even when the
¾
power is turned off.
However setting function is effective after power reset.
Record the function set in the indoor unit on a label, etc., and afx the label to the
unit so it can be used for after-sales service operations.
- (07-109) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Other manuals for Fujitsu Airstage J-II

Related product manuals