EXTERNAL OUTPUT1-1-2.
Connector Output voltage Status
CN136 (Black) 0V Normal
DC 12-24 V *4 Error
CN137 (Blue) 0V Stop
DC 12-24 V *4 Operation
ERROR STATUS (Master unit only)
This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error" status.
OPERATION STATUS (Master unit only)
This output indicates the outdoor unit's "Operation" status.
*4: Provide a DC12 to 24V power supply.
Select a power supply capacity with an ample
surplus for the connected load.
*5: The allowable current is 30mA or less.
Provide a load resistance such that the current
becomes 30mA or less.
*6: Polarity is [+] for pin 1 and [-] for pin 2.
Connect correctly.
Do not impress a voltage exceeding 24V across
pins 1-2.
1
2
+
+
-
-
CN136
(Black)
or CN137
(Blue)
connected unit
DC power supply
(External) 12 - 24V
Connected
load (Operation
Indicator or Error
Indicator)
*6
*4
*5
P.C. B
CN137
Output
CN136
Output
Operation
Error
12 - 24V
12 - 24V
0V
0V
Stop
Normal
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
BASE HEATER
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
*7: Connect to pin 1 and pin 3. No connection pin2 and pin4.
*8: The allowable current is 1A or less.
1
2
3
4
CN115
(Black)
Voltage: power supply
input voltage
Base heater
*8
*7
P.C. B
AWG18 (0.82mm
2
)
- (08 - 05) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT