INPUT SIGNAL TYPE
The input signal type can be selected.
It is switched by Dip-Sw on the indoor unit PCB.
(
u
...Factory setting)
Dip-sw [Set 2-2] Input signal type
u
OFF Edge
ON Pulse
Note: input signal type of Ch3 (Forced thermostat off) is only "Edge".
CONTROL INPUT FUNCTION
When function setting is "Operation/Stop" mode
z
In the case of "Edge" input
Connector Input signal Command
Ch1 of
CNA01 or CNA02
OFF → ON Operation
ON → OFF Stop
Ch1 input of
CNA01 or
CNA02
Remote
Controller
Indoor unit
Operation
On
On
Off
Stop
In the case of "Pulse" input
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF → ON Operation
Ch2 OFF → ON Stop
Operation
On
On
The width of pulse must be longer than 200msec.
Off
Off
Stop
CNA01
or
CNA02
Ch1 input
Ch2 input
Remote
Controller
On
Indoor unit
NOTE :
The last command has priority.
The indoor units within the same remote controller group operates in the same mode.
Pulse
Edge
- (08 - 11) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT