EXTERNAL OUTPUT1-2-2.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
Use an external input and output cable with appropriate external dimension, depending on the number of cables
to be installed.
Output voltage: Hi DC12V±2V, Lo 0V.
Permissible current: 50mA
Connector Output voltage Status
CNB01
External output1
Pins 1-2
0V Stop
DC 12V Operation
External output2
Pins 1-3
0V Normal
DC 12V Error
External output3
Pins 1-4
0V Indoor unit fan stop
DC 12V Indoor unit fan operation
External output4
Pins 1-5
0V Auxiliary heater OFF
DC 12V Auxiliary heater ON
OUTPUT SELECT
When indicator etc. are connected directly
z
1
2
3
4
5
6
+
-
-
-
P.C. B
CNB01
Operation
indicator
Error indicator
Indoor unit Fan
status indicator
connected unit
When connecting with unit equipped with a power supply
z
1
2
3
4
5
6
+
-
-
-
-
P.C. B
CNB01
Connected
device 1
Connected
device 2
Connected
device 3
Heater
connected unit Relay