Apply voltage terminal ([CNA02])
z
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal ([CNA02])
1
2
3
+
+
-
-
Input device
Load
resistance
*1
DC power
supply 12 - 24V
connected unit
P.C. B
CNA02
*c
*d
*1: Make the power supply DC12 to 24V. Select a power supply capacity with an ample surplus for the
connected load.
Do not impress a voltage exceeding 24V across pins 1-3.
*c: The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*d: The polarity is [+] for pin 1 and [-] for pin 3. Connect correctly.
When connected to Apply voltage terminals of multiple RB units with a connected unit, be sure
to make a branch outside the RB unit using a pull box, etc. as shown on below example.
Input device
RB unitRB unitRB unit
Load
resistance
DC power
supply 12 - 24V
connected unit
P.C. B
P.C. B
P.C. B
CNA
02
CNA
02
CNA
02
- (08 - 27) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT