OPTIONAL PARTS INSTALLATION10.
DRAIN PUMP UNIT10-1.
MODEL : UTZ-PX1BBA
Specications
z
Unit Specications
Height of drain up mm Maximum 1000
Power source - 220-240V, 50/60Hz
Input Power (230V, 50/60Hz) W 12 / 10.8
Current (230V, 50/60Hz) mA 114 / 92
Dimensions (H x W x D) mm 176 x 178 x 154
Weight kg 2.5
Connection pipe diameter - VP25 (I.D.25mm, O.D.32mm)
Direction of pipe connection
*
1 - 360°
Angle of pipe connection
*
2 - 0° (Horizontal)-90° (Vertical)
Control method - Control board of indoor unit
safety device - Float switch, Thermal fuse
*
1 : Direction of pipe connection
*
2 : Angle of pipe connection
Application indoor units
z
Type Model name
Low Static Pressure
Duct / Concealed Floor
ARXB07GALH, ARXB09GALH, ARXB12GALH,
ARXB14GALH, ARXB18GALH
Mounting position
z
Connected drain pipe (VP25)
(I.D. 25mm; O.D.32mm)
Front view
(Unit : mm)
Front view
Right
side
Left
side
Strong and slide ceiling
470 or more100 or more
154
127
720
178
390
167
38
597 * / 886 *
3 4
560 * / 850 *
3 4
575
Drain pump unit
Top view
Air
Note:
Leave the space required to service the unit.
Set a maintenance hole near the drain pump unit.
This product is specially designed for ceiling concealed
installation of the indoor unit.
It cannot be connected when it is installed on the oor.
*3 : ARXB07, 09
*4 : ARXB12, 14, 18
- (10 - 57) -