PRECAUTION
● Select the installation location that meets the following requirement and that is approved by the
customer.
• Cold and warm air should reach the entire room.
Installation height *1
D≦1000 mm
D
floor
*2
*1) Refer to Design & Technical manual for Air velocity distribution and Air temperature distribution during heating.
*2) If the distance from the ceiling is not adequate, it may cause mildew stains on the wall or the ceiling. (Ensure to x
at least 150 mm away from any surface of the equipment.)
● Do not install the unit in the following areas
• The upper part of the vicinity of room entrance. It may cause condensation on the outlet port.
• Near a wall surface. It may cause condensation on the wall during cooling.
• Area lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen.
• The place where it will be exposed to direct sunlight. Or else, it may cause a change in color.
● When the installation area is exposed to direct sunlight, take measures to block the light such as
covering the grille surface with a sheet. Or else, it may cause a change in color.
● Use an appropriate Grille that is compatible with the indoor unit. If not used with the correct
combination, it may cause condensation.
● Perform heat insulation and eld setting according the Design & Technical manual of Indoor unit.
Not installing as per the instructions may cause condensation.