Model name ASUA30TLAV2 ASUA36TLAV2
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 30,000 34,000
kW 8.8 10.0
Heating
Btu/h 34,000 38,000
kW 10.0 11.2
Input power W 74 103
Fan
Airflow rate
HIGH
CFM (m
3
/h)
848 (1,440)
954/895*
1
(1,620/1520
*
1
)
MED—HIGH 707 (1,200) 766 (1,300)
MED 618 (1,050) 660 (1,120)
MED—LOW 554 (940) 577 (980)
LOW 524 (890) 524 (890)
QUIET 412 (700) 412 (700)
Type × Q'ty Crossflow × 1
Motor output W 61
Sound pressure level*
2
HIGH
dB (A)
53
55/54*
1
MED—HIGH 49 51
MED 45 47
MED—LOW 42 43
LOW 39 39
QUIET 33 33
Heat exchanger type
Length in (mm)
Main: 35-7/16 (900)
Sub1: 35-7/16
(900)
Sub2: 35-7/16 (900)
Fin pitch FPI
Main: 21
Sub1: 18
Sub2: 18
Rows × Stages
Main: 2 × 22
Sub1: 1 × 6
Sub2: 1 × 4
Face area
ft
2
(m
2
)
4.5 (0.42)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP plain weave
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
13-3/8 × 45-1/4 × 11 (340 × 1,150 × 280)
Gross 15-5/16 × 50 × 17-11/16 (405 × 1,270 × 450)
Weight
Net
lb (kg)
40 (18)
Gross 53 (24)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 3/8 (9.52)
Gas (Flare) Ø 5/8 (15.88)
Drain hose I.D.: Ø 9/16 (13.8); O.D.: Ø 5/8 to 11/16 (15.8 to 16.7)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: This value is “Cooling operation/Heating operation”.
*2: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.