Confirm whether satisfy the following calculation.
If A is lower than B, go to step marked [▼▼▼].
Total capacity of indoor units at design tempera-
ture ≥ compensated capacity of outdoor units
(A ≥ B)
↓
System capacity = B
↓
Calculate actual capacity of each indoor unit by
dividing system capacity proportionally.
Refer to "Capacity calculation method" on page
02-4.
↓
Confirm whether satisfy the following calculation.
If actual capacity of indoor unit is lower than
heat load, change to larger capacity of outdoor
units and return to step marked [▲▲].
If actual capacity of indoor unit is greater than
heat load, procedure is completing.
Actual capacity of indoor unit ≥ heat load
↓
End
[▼▼▼]
System capacity = A
↓
Actual capacity of indoor unit = capacity of in-
door unit at design temperature
↓
End
1-2. Indoor unit and outdoor unit selection procedure - (02-3) - 1. Model selection and capacity calculation