1-2. Indoor unit and outdoor unit selection procedure
Confirm the design of indoor and outdoor tem-
perature condition.
Calculate heat load of each room.
Select indoor unit to match the heat load for
each room.
[▲]
Calculate the estimated capacity of each indoor
unit.
Refer to "Capacity calculation method
" on page
02-4.
Confirm whether satisfy the following calculation.
If estimated capacity is lower than heat load,
change to larger capacity of indoor unit and re-
turn to step marked [▲] and perform the calcula-
tion again.
Estimated capacity of indoor unit ≥ heat load
Calculate the total capacity of indoor units at fol-
lowing conditions:
Calculated total capacity of indoor units: A
Rated condition
Design temperature condition
[▲▲]
Select outdoor units to match the total capacity
of indoor units.
Refer to "Cooling capacity range of connectable
indoor units" on page 02-12.
Confirm the following items:
Cooling capacity range of connectable in-
door units
Maximum connectable indoor units number
Calculate the compensated capacity of outdoor
units.
Refer to "Capacity calculation method" on page
02-4.
Calculated compensated capacity of outdoor
units: B
1-2. Indoor unit and outdoor unit selection procedure - (02-2) - 1. Model selection and capacity calculation
MODEL
SELECTION
MODEL
SELECTION