¢ Functions
Function Remarks
Air conditioning
control function
Operation mode setting Cooling, Heating, Fan
Fan speed setting HIGH, MED, LOW, AUTO
Temperature setting
Stage 1 (Cooling), Stage 1 (Heating)
Stage 2 (Cooling), Stage 2 (Heating)
Maintenance
function
Indoor unit error monitoring
Communication error detection
Control target error indication
Convertor error monitoring
Others
Two-stage cooling and heating
thermostat operation
Delay off
¢
L
imitation
Automatic prohibition of remote controller operation
Thermostat operates the indoor units according to the setting temperature by built-in temperature
sensor. Since setting temperature of the remote controller may be different from the setting tem-
perature of the thermostat, remote controller operation prohibition is automatically enabled.
Air direction adjustment by thermostat
No fan mode is available in heat pump system.
Do not connect between fan signal terminals (G, G1, G2, or G3) on the convertor and the thermo-
stat by using wire.
Error code will be displayed on the built-in LED display.
For indoor unit without error code indicator, confirm the LED display inside the thermostat conver-
tor. For details of indoor unit error, refer to the "Error status (External output 2)" in Chapter 8. EX-
TERNAL INPUT AND OUTPUT on page 08-35
.
For following items, use remote controller.
Filter sign cancellation
Indoor unit function settings
Test run
After all settings are completed, disconnect the remote controller, and connect the Thermostat
convertor.
3-5. Thermostat convertor (UTY-TTRX) - (05-139) - 3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM