Electrical wiring
Fuse (1.25 A)
Outdoor unit
Switch
Transmission cable
General purpose building control computer
(BMS)
Power supply cable
Master or Slave
Outdoor unit
1Φ 50/60 Hz
208-240 V
BACnet gateway
Indoor unit
C2
RJ45
A B SGND
BACnet gateway
BACnet gateway
Power supply
Ethernet cable to BMS
Indoor unit
Transmission cable
NOTES:
Do not bind the power supply cable and transmission cable to avoid an erroneous operation.
Use shield cable for transmission cable. The shield metal should be grounded.
Do not forget to ground the BACnet gateway.
¢ F
unctions
Indoor unit control
Individual control
Commands from BACnet network are sent to the respective indoor units.
(BACnet network → respective indoor units of VRF network)
Batch control
Commands from BACnet network are sent to all indoor units connected to VRF network.
(BACnet network → All indoor units of VRF network)
Indoor unit status monitoring
Indoor unit status is communicated to the BACnet network in the form of BACnet objects.
(BACnet network ← All indoor units of VRF network)
3-6. BACnet gateway (Hardware: UTY-VBGX) - (05-146) - 3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM