Control and monitoring items with object types
Function name
Category BACnet
object
type*
1
Remarks
Target Monitor Control
Operation setting*
2
Bat — ○ BO
Operation mode Bat — ○ MO
Temperature setting Bat — ○ AO
Fan speed Bat — ○ MO
R/C prohibition Bat — ○ MO
Gateway GW ○ — D No monitor/control difference
Representative error GW ○ — BI Gateway, Lon communication
Error code GW ○ — MI
Gateway, Lon communication
Error codes to signal gateway status
will be agreed with FGL during
development.
Energy saving status/setting GW ○ ○ BI/BO
Existence check In ○ — BI
Temperature status/setting In ○ ○ AI/AO
Operation status/setting In ○ ○ BI/BO
Operation mode status/setting In ○ ○ MI/MO
Fan speed status/setting In ○ ○ MI/MO
Suction/Room temperature In ○ — AI
Representative error In ○ — BI
Error code In ○ — MI
Temperature H/L limit status/
setting
In ○ ○ AI/AO
H/L limit per 3 operation Mode:
HEAT,
COOL-DRY, and AUTO
Temperature limit validity
status/setting
In ○ ○ BI/BO
Filter sign status/reset In ○ ○ BI/BO Only reset for control
Forced thermo off status/
setting*
3
In ○ ○ BI / BO
Emergency stop In ○ — BI
R/C prohibition status/setting In ○ ○ MI/MO
Vertical fan status/setting In ○ ○ MI/MO
Horizontal fan status/setting In ○ ○ MI/MO
Outdoor unit save status/
setting
Out ○ ○ MI/MO
Low noise operation status/
setting
Out ○ ○ MI/MO Monitor not supported by all
Representative error Out ○ — BI
Error code Out ○ — MI
Forced off status/setting Out ○ ○ BI/BO
3-6. BACnet gateway (Hardware: UTY-VBGX) - (05-147) - 3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM