Central drain process
When conveying multiple drain pipes, install according to the procedure shown below.
For Compact cassette type, and Circular flow cassette type, and Cassette type
4 in. (100 mm) or more
A
T-joint converging drain pipes
VP30 (O.D. 1-1/2 [38 mm]) or more
Downward gradient 1/100 to 1/50
A
Compact cassette type 28 in (700 mm) or less
Circular flow cassette type
type
Cassette type
34 in (850 mm) or less
For High static pressure duct
type
4 in (100 mm) or more
For Mini duct
type and Slim duct type
28 in (700 mm)
or less
Select converging drain pipes whose diameter is suitable for the operating capacity of the unit.
5-2. Indoor unit - (06-75) - 5. Drain connection
SYSTEM
DESIGN
SYSTEM
DESIGN