Drain insulation
Confirm water flows into drain pan of the indoor unit and drains from the pan once the drain hose
is connected.
Check drain pipes for leaks.
Insulate the drain to prevent condensation.
Secure the drain pipe to the wall with a saddle.
Pipe
S
addle
Wall
Outside wall cap
Sealer putty
(Outdoors)
Seal the hole around drain pipe with caulk.
Silicone sealant
Heat insulation
adhesive tape
Be sure to coat the entire and surface. Is there is a gap it could cause condensation.
5-2. Indoor unit - (06-76) - 5. Drain connection
SYSTEM
DESIGN
SYSTEM
DESIGN