¢ Indoor unit addresses and setting ranges
Setting
Setting
range
Type of switch Remarks
D
Refrigerant circuit
address
00—99
Manual address setting:
Arbitrary numbers can be set in
range of 00—99.
Setting example
01
REF AD
x10
REF AD
x1
Wireless R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wireless remote controller
" on
page 07-15.
Wired R. C. (3-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (UTY-
RNKU)" on page 07-26.
Simple R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
simple remote controller (UTY-
RSRY and UTY-RHRY)" on
page 07-31.
Wired R. C. (2-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (Touch
panel) (UTY-RNRUZ)" on
page 07-44.
Automatic address setting:
This switch is set to 00 at factory
setting.
Refer to "Automatic address
setting of indoor unit
" on page
07-52.
E Indoor unit address 00—63
Manual address setting:
Arbitrary numbers can be set in
range of 00—63.
Setting example
12
IU AD
x1
0
IU AD
x1
Wireless R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wireless remote controller
" on
page 07-15.
Wired R. C. (3-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (UTY-
RNKU)" on page 07-26.
Simple R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
simple remote controller (UTY-
RSRY and UTY-RHRY)" on
page 07-31.
Wired R. C. (2-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (Touch
panel) (UTY-RNRUZ)" on
page 07-44.
Automatic address setting:
This switch is set to 00 at factory
setting.
Refer to "Automatic address
setting of indoor unit
" on page
07-52.
F
Remote controller
address
00—15
Manual address setting:
3-wire type R. C. can be set in
range of 0—15.
Setting example
10
RC AD
Wireless R. C.:
This switch is set to 0 at factory
setting.
2-wire type only.
1-2. Address setting - (07-4) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS