¢ Addresses and setting ranges for controllers, convertors or
other devices
Unit Setting
Setting
range
Type of switch Setting references
Touch panel
controller
G
Controller
address
00—15
*
1
Automatic address setting:
This switch is set to 00 at factory
setting.
"Touch panel controller"
on page 07-
105"Touch
panel controller" on
page 07-105
Network convertor H
Convertor
address
00—15
*
1
"Network convertor
(UTY-VTGX)"
on page
07-115 and "Network
convertor (UTY-
VGGXZ1)" on page 07-
117
Refrigerant
circuit address
00—99
Setting
example 01
SW 110 SW 111
(10 digit) (1 digit)
Wired, simple
remote controller
(3-wire type)
J
Dual remote
control
ON/OFF Switch 2 of DIP switch 1
"Wired remote controller
(UTY-RNKU
)" on page
07-101
"Simple remote
controller (UTY-RSKU,
UTY-RHKU)" on page
07-103
Signal amplifier K
Signal amplifier
address
1—8
Manual address setting
"Signal amplifier" on
page 07-119
Automatic address setting:
This switch is set to 1 at factory
setting.
"Automatic address
setting of signal
amplifier" on page 07-
50
Modbus convertor Q
Controller/
convertor
address
00—15
*
1
"Modbus convertor for
VRF" on page 07-
121"Modbus convertor
for VRF" on page 07-
121
Network convertor
for LonWorks
M
"Network convertor for
LonWorks" on page 07-
124
Central remote
controller
N
"Central remote
controller (UTY-DCGY)"
on page 07-106
"Central remote
controller (UTY-
DCGYZ1)" on page 07-
107
Wired remote
controller
(2-wire type)
F
Remote
controller
address
1—32 *
2
Manual address setting
"Wired remote controller
(Touch panel)" on page
07-109
0—15 Automatic address setting
Dual remote
control
ON/OFF
*
1
: The sum total of the
Touch panel controller, Central remote controller, Network convertor for
Group remote controller, Modbus convertor, and Network convertor for LonWorks is a maximum
of 16.
NOTE: For Touch panel controller, Central remote controller, Network convertor for Group re-
mote controller, Modbus convertor, and Network convertor for LonWorks connected in
same VRF network system, set an exclusive address on each device.
*
2
: The address can be set in the range of 1 to 32. However, do not set the same number as that
for the remote controller address of an indoor unit connected using the same remote-control ca-
ble.
1-2. Address setting - (07-5) - 1. System settings