5. Send the information by pressing the START/STOP button once. A beeping sound (2 short
beeps, 1 long beep, 2 short beeps, and 1 long beep) will be emitted if the command is accept-
ed.
Beeps are emitted
intermittently
(2 short beeps,
1 long beep, 2 short beeps,
and 1 long beep)
In the following cases, the setting signal will not be accepted correctly and 5 short beeps will be
emitted:
• The indoor unit address number is set out of range (64 or more)
• The setting of the rotary switch on the indoor unit PCB is not set to “00”
6. Indoor unit lamps will indicate the indoor unit address data number as follows:
OPERATION
(Green)
TIMER
(Orange)
Lit continuously Flashes times of
address numbers
(the left digit)
FILTER
(Red)
Flashes times of
address numbers
(the right digit)
Example) ADDRESS: 34
OPERATION lamp
(Green)
TIMER lamp
(Orange)
FILTER lamp
(Red)
0.5 sec ON / 0.5 sec OFF
4 times
3 times 1 to 10 sec
1 to 10 sec
0.5sec ON / 0.5sec OFF
When the address setting is “0”, TIMER lamp and FILTER lamp will not flash.
C
onfirmation of address setting
To confirm the address setting is properly configured, press the TIMER set (+) button.
TIMER set (+) button
Correct:
Beeps are emitted intermittently as follows:
(2 short beeps,
1 long beep, 4 short beeps,
and 1 long beep)
Wrong:
(
3 sec)
(2 short beeps and 1 long beep)
1-4. Address setting by remote controller - (07-20) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS