5. Send the information by pressing the START/STOP button once. A beeping sound (2 short
beeps, 1 long beep, 2 short beeps, and 1 long beep) will be emitted if the command is accept-
ed.
Beeps are emitted
intermittently
(2 short beeps,
1 long beep, 2 short beeps,
and 1 long beep)
In the following cases, the setting signal will not be accepted correctly and 5 short beeps will be
emitted:
The indoor unit address number is set out of range (64 or more)
The setting of the rotary switch on the indoor unit PCB is not set to “00”
6. Indoor unit lamps will indicate the indoor unit address data number as follows:
OPERATION
(Green)
TIMER
(Orange)
Lit continuously Flashes times of
address numbers
(the left digit)
FILTER
(Red)
Flashes times of
address numbers
(the right digit)
Example) ADDRESS: 34
OPERATION lamp
(Green)
TIMER lamp
(Orange)
FILTER lamp
(Red)
0.5 sec ON / 0.5 sec OFF
4 times
3 times 1 to 10 sec
1 to 10 sec
0.5sec ON / 0.5sec OFF
When the address setting is “0”, TIMER lamp and FILTER lamp will not flash.
C
onfirmation of address setting
To confirm the address setting is properly configured, press the TIMER set (+) button.
TIMER set (+) button
Correct:
Beeps are emitted intermittently as follows:
(2 short beeps,
1 long beep, 4 short beeps,
and 1 long beep)
Wrong:
(
3 sec)
(2 short beeps and 1 long beep)
1-4. Address setting by remote controller - (07-20) - 1. System settings