LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
2 1
Operation
mode selecting
method
0 0
Priority given to the first
command
♦
Select the priority setting of the
operation mode.
•
Priority given to the first
command: Priority is given to
the operation mode which is
set first.
0 1
Priority given to external
input of outdoor unit
• Priority given to external input
of outdoor unit: Priority is
given to the operation mode
which is set by the external
input terminal (CN132).
0 2
Priority given to
administrative indoor
unit
• Priority given to administrative
indoor unit: Priority is given to
the operation mode of the
administrative indoor unit
which is set by the wired
remote controller.
2 2 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
2 3 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
2 4 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
2 5 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
2 6 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
2 7 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
2 8
Change of unit
(Temperature)
0 0 Celsius (°C) ♦
0 1 Fahrenheit (°F)
2 9
Change of unit
(Pressure)
0 0 MPa ♦
0 1 psi
3 0
Outdoor unit
capacity save
setting
0 0 Level 1 (Stop) ♦ The capacity limit in Energy saving
peak cut control operation can be
selected. With lowering the level,
the energy efficiency get higher
but the cooling or heating
performance gets lower.
0 1 Level 2
0 2 Level 3
0 3 Level 4
0 4 Level 5
3 1 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
3 5
Presence of
heater
selection
control using
outdoor
temperature
0 0 Disabled ♦ For heater control switching,
setting of heater selection control
using outdoor temperature 1 and 2
is required. (Setting value of
function setting number 61 on
indoor unit: 03 or 04)
For details, refer to "External
output" in Chapter 8. EXTERNAL
INPUT AND OUTPUT on page 08-
5.
0 1 Enabled
2-1. Setting on outdoor unit PCB - (07-64) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS