LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
3 6
Outdoor
temperature
zone boundary
temperature A
0 0 -4.0 °F (-20 °C) ♦ Setting if changing the outdoor
temperature setting for heat pump
prohibition zone is required when
heater selection control using
outdoor temperature 1 and 2 are
performed on indoor unit.
For details, refer to "External
output" in Chapter 8. EXTERNAL
INPUT AND OUTPUT on page 08-
5.
0 1 -0.4 °F (-18 °C)
0 2 3.2 °F (-16 °C)
0 3 6.8 °F (-14 °C)
0 4 10.4 °F (-12 °C)
0 5 14.0 °F (-10 °C)
0 6 17.6 °F (-8 °C)
0 7 21.2 °F (-6 °C)
0 8 24.8 °F (-4 °C)
3 7
Outdoor
temperature
zone boundary
temperature B
0 0 42.8 °F (6 °C) ♦
Setting if changing the outdoor
temperature setting for heat pump
only zone is required when heater
selection control using outdoor
temperature 1 is performed on
indoor unit.
For details, refer to "External
output" in Chapter 8. EXTERNAL
INPUT AND OUTPUT on page 08-
5.
0 1 14.0 °F (-10 °C)
0 2 17.6 °F (-8 °C)
0 3 21.2 °F (-6 °C)
0 4 24.8 °F (-4 °C)
0 5 28.4 °F (-2 °C)
0 6 32.0 °F (-0 °C)
0 7 35.6 °F (2 °C)
0 8 39.2 °F (4 °C)
0 9 42.8 °F (6 °C)
1 0 46.4 °F (8 °C)
1 1 50.0 °F (10 °C)
1 2 53.6 °F (12 °C)
1 3 57.2 °F (14 °C)
1 4 60.8 °F (16 °C)
1 5 64.4 °F (18 °C)
4 0
Capacity
priority setting
(in low noise
mode)
0 0 Off (Quiet priority) ♦ If the cooling/heating performance
becomes insufficient when the low
noise mode is set, it is possible to
set “Capacity priority” that
automatically cancels the low
noise mode. (Once performance is
restored, the mode will
automatically return to the low
noise mode.)
0 1 On (Capacity priority)
4 1
Low noise
mode setting
0 0 Off (Normal) ♦
0 1 On (Low noise mode)
4 2
Low noise
mode operation
level setting
0 0 Level 1 ♦
Level 1: The operating sound
lowers from about 3 to 5 dB (A)
more than the rated value.
0 1 Level 2
Level 2: The operating sound
lowers from about 3 to 5 dB (A)
more than the Level 1.
6 0 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
7 0
Electricity
meter no.
setting 1 *
1
0 0 Setting number x00 ♦
Set the ones digit and tens digit of
the number of the electricity meter
connected to CN135.
0 1 Setting number x01
•
•
•
•
•
•
•
•
•
9 8 Setting number x98
9 9 Setting number x99
7 1
Electricity
meter no.
setting 2 *
1
0 0 Setting number 0xx ♦
Set the hundreds digit of the
number of the electricity meter
connected to CN135.
0 1 Setting number 1xx
0 2 Setting number 2xx
2-1. Setting on outdoor unit PCB - (07-65) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS