LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
7 2
Electricity
meter pulse
setting 1 *
2
0 0 Setting number xx00
Set the ones digit and tens digit of
the number of the electricity meter
pulse setting connected to CN135.
0 1 Setting number xx01
9 8 Setting number xx98
9 9 Setting number xx99
7 3
Electricity
meter pulse
setting 2 *
2
0 0 Setting number 00xx
Set the hundreds digit and
thousands digit of the electricity
meter pulse setting connected to
CN135.
0 1 Setting number 01xx
9 8 Setting number 98xx
9 9 Setting number 99xx
9 0 Prohibited
0 0 Prohibited
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
0 4 Prohibited
0 5 Prohibited
0 6 Prohibited
0 7 Prohibited
0 8 Prohibited
0 9 Prohibited
1 0 Prohibited
1 1 Prohibited
*
1
: When electricity meter number is set to “000” and “201 to 299”, the pulses input to CN135 be-
come ineffective. Available setting number is “001” to “200”.
*
2
: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135 become inef-
fective. Available setting number is “0001” to “9999”.