6. Confirm the setting by pressing the START/STOP
button. The data will be transferred to the
indoor unit.
• When the setting is properly set up on the indoor unit, the set number will be displayed.
(GOOD)
•
When the setting is not set up correctly, “- -” is displayed. (ERROR) Back to the previous step
and perform the setting again.
RELATED LINKS
"Completion of setting mode" on page 07-43
"Function details" on page 07-96
¢ S
etting up each indoor unit
Setting must be performed on each indoor unit by repeating following procedures.
• "Preparation
" on page 07-90
• "Indoor unit function setting" on page 07-91
Simple remote
controller
S
imple remote
controller
Simple remote
controller
0001 0101 0201 1301 1401 15010 1 2 0 1 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
¢
R
esetting the power after setting up all indoor units
NOTES:
•
If the reset is not performed, function cannot be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
2-7. Indoor unit (setting by UTY-RSKU, UTY-RHKU) - (07-92) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS