Function
Function
number
Setting number
Factory
setting
Details
Control
switching of
external
heaters
62
00 Setting 0 ♦
Sets the temperature conditions when the external
heater is on.
For the temperature conditions, refer to "Temperature
conditions when the external heater is on/off" on
page 07-
100.
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
06 Setting 6
07 Setting 7
08 Setting 8
09 Setting 9
10 Setting 10
11 Setting 11
12 Setting 12
13 Setting 13
14 Setting 14
15 Setting 15
16 Setting 16
17 Setting 17
Auto mode
type
68
00
Single setpoint
auto mode
(traditional)
♦
Switches the setting method of auto mode to single or
dual (cooling/heating).
For heat pump systems, it is necessary to set the
master indoor unit by using wired remote controller.
NOTE: Auto mode type will be usable provided
that the corresponding operating device is
connected.
01
Dual setpoint auto
mode
Deadband
value
69
00 0 °F (0 °C) ♦
Choose the minimum temperature between cooling
and heating settings (deadband) for dual setpoint
auto mode (function number 68).
NOTE: Deadband value will be usable provided
that the corresponding operating device is
connected.
01 0.9 °F (0.5 °C)
02 1.8 °F (1.0 °C)
03 2.7 °F (1.5 °C)
04 3.6 °F (2.0 °C)
05 4.5 °F (2.5 °C)
06 5.4 °F (3.0 °C)
07 6.3 °F (3.5 °C)
08 7.2 °F (4.0 °C)
09 8.1 °F (4.5 °C)
Standby
time for
auxiliary
equipment
operation
71
00 Disabled ♦
Sets the standby time until the auxiliary equipment
operation starts during primary equipment operation.
For details, refer to "External output" in Chapter 8.
EXTERNAL INPUT AND OUTPUT on page 08-5.
01 1 minute
02 2 minutes
• •
• •
• •
98 98 minutes
99 99 minutes
Heat pump
backup
setting
72
00 Disabled ♦ Enables or disables the heat pump backup instruction
from the outdoor unit. This function will be usable
provided that the corresponding outdoor unit is
connected.
01 Enabled
Emergency
heat
73
00 Disabled ♦
Enables or disables the emergency heat input.
01 Enabled
Fan delay
time
74
00 1 minute ♦
Sets the fan delay time when the heater is turned off.
01 50 seconds
02 40 seconds
03 30 seconds
2-9. Function details - (07-99) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION