ALPS Advanced Line Protection System B-11
APPENDIX B B.2 REGISTER MAPS
B
3290 Z4TIMETRIP R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3291 Z1PHASTRIP R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3292 ANYZ2PHASE R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3293 CONFGTRIP R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
PROTECTION SETTINGS: LINE PICKUP
3294 LINEPICKUP R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3295 BYPASSTL3 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3296 I1PICKUP R/W P10 1 2 to 30 10 to 150 A 20 100
3297 REMOTEOPEN R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3298 TL20PICKUP R/W Unsi
g
ned Int 1 10 to 100 ms -
PROTECTION SETTINGS: LINE OVERLOAD
3299 LINEOVERLD R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3300 LEVEL1PU R/W P10 1 5 to 40 25 to 200 A 20 100
3301 LEVEL2PU R/W P10 1 10 to 80 50 to 400 A 40 200
3302 LEVEL1TDLY R/W Unsi
g
ned Int 1 10 to 200 sec. 50
3303 LEVEL2TDLY R/W Unsi
g
ned Int 1 10 to 99 sec. 25
PROTECTION SETTINGS: SCHEME
3304 PICKSCHEME R/W Unsi
g
ned Int 1 0 =STEPDST, 1=PUTT,
2=POTT1, 3=POTT2,
4=HYBRID, 5=BLOCK,
6=HYBRID BLOCK
-0
3305 NUMRCVR R/W Unsi
g
ned Int 1 0, 1, 2 - 0
3306 TRIPMODE R/W Unsi
g
ned Int 1 0=3POLE, 1=1POLE,
2=1POLEZ2
-0
3307 CARRSTART R/W Unsi
g
ned Int 1 0=DIR, 1=IPB, 2=FD - 1
3308 WKINFTRIP R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
PROTECTION SETTINGS: SCHEME TIMERS
3309 TL1PICKUP R/W Unsi
g
ned Int 1 1 to 200 ms 5
3310 TL4PICKUP R/W Unsi
g
ned Int 1 0 to 50 ms 0
3311 TL4DROPOUT R/W Unsi
g
ned Int 1 0 to 50 ms 0
3312 TL5PICKUP R/W Unsi
g
ned Int 1 0 to 200 ms 50
3313 TL5DROPOUT R/W Unsi
g
ned Int 1 0 to 200 ms 50
3314 TL6PICKUP R/W Unsi
g
ned Int 1 0 to 200 ms 50
3315 TL6DROPOUT R/W Unsi
g
ned Int 1 0 to 200 ms 50
3316 TL16PICKUP R/W Unsi
g
ned Int 1 8 to 99 ms 8
3317 TL24DROPOUT R/W Unsi
g
ned Int 1 30 to 500 ms 30
3318 TL25DROPOUT R/W Unsi
g
ned Int 1 30 to 500 ms 30
3319 TL26PICKUP R/W Unsi
g
ned Int 1 0 to 50 ms 0
PROTECTION SETTINGS: LINE INFORMATION
3320 POSSEQANG R/W Unsi
g
ned Int 1 25 to 90 de
g
85°
3321 ZERSEQANG R/W Unsi
g
ned Int 1 25 to 90 de
g
75°
3322 ZLINE R/W P100 1 5 to 25000 1 to 5000 3000 600
3323 ZEROSEQK0 R/W P100 1 100 to 700 - 300
3324 LINELENGTH R/W P10 1 0 to 5000 mi/km 1000
3325 LINEUNIT R/W Unsi
g
ned Int 1 0=Miles, 1=Km - 0
3326 CTRATIO R/W Unsi
g
ned Int 1 1 to 5000 - 2000 400
3327 VTRATIO R/W Unsi
g
ned Int 1 1 to 7000 - 3000
Table B–4: MODBUS MEMORY MAP (Sheet 7 of 10)
ALPS
REGISTER
CONTENTS TYPE FORMAT NO. OF
REGS.
RANGE UNITS DEFAULT