B-12 ALPS Advanced Line Protection System
GE Power Management
B.2 REGISTER MAPS APPENDIX B
B
PROTECTION SETTINGS: SCADA DTA
3328 FLTLOCK R/W P10 1 0 to 999 sec. 0
3329 FLTRESET R/W Unsi
ned Int 1 0 to 999 min. 0
PROTECTION SETTINGS: OUT-OF-STEP BLOCKING
3330 MOBZONE R/W Unsi
ned Int 1 0=Zone2, 1=Zone3, 2=Zone4 - 1
3331 MOBCHARANG R/W Unsi
ned Int 1 30 to 130 de
70°
3332 BLOCKWHAT R/W Unsi
ned Int 1 0=BLKALL, 1=BLKDIST,
2=BLKPHAS, 3=BLKNONE
-0
3333 BLOCKZ1 R/W Unsi
ned Int 1 0=No, 1=Yes - 1
3334 BLOCKZ2 R/W Unsi
ned Int 1 0=No, 1=Yes - 1
3335 BLOCKZ3 R/W Unsi
ned Int 1 0=No, 1=Yes - 1
3336 BLOCKZ4 R/W Unsi
ned Int 1 0=No, 1=Yes - 1
PROTECTION SETTINGS: OUT-OF-STEP TRIPPING
3337 USE_OST R/W Unsi
ned Int 1 0=No, 1=Yes - 0
3338 NUMBRCHAR R/W Unsi
ned Int 1 2, 3 - 3
3339 TRIPIN_OUT R/W Unsi
ned Int 1 0=In, 1=Out - 1
3340 FWDREACH R/W P10 1 5 to 3750 1 to 750 Ω 750 150
3341 REVREACH R/W P10 1 5 to 3750 1 to 750 Ω 250 50
3342 OUTER R/W Unsi
ned Int 1 40 to 165 de
90°
3343 MIDDLE R/W Unsi
ned Int 1 40 to 165 de
105°
3344 INNER R/W Unsi
ned Int 1 40 to 165 de
120°
3345 TLOS1PU R/W Unsi
ned Int 1 1 to 100 ms 40
3346 TLOS1DO R/W Unsi
ned Int 1 1 to 100 ms 40
3347 TLOS2PU R/W Unsi
ned Int 1 1 to 100 ms 40
3348 TLOS3PU R/W Unsi
ned Int 1 1 to 100 ms 40
3349 TLOS4PU R/W Unsi
ned Int 1 1 to 100 ms 40
PROTECTION SETTINGS: RECLOSER
3350 RECLMODE R/W Unsi
ned Int 1 0=None, 1=Internal,
2=External, 3=Off
-3
3351 RECTYPE R/W Unsi
ned Int 1 0=3POLE, 1=1POLE,
2=1POLE/3POLE
-0
3352 NUM_1P R/W Unsi
ned Int 1 1 to 4 - 1
3353 1PDELAY1 R/W P10 1 1 to 3000 sec. 1
3354 1PDELAY2 R/W P10 1 1 to 3000 sec. 1
3355 1PDELAY3 R/W P10 1 1 to 3000 sec. 1
3356 1PDELAY4 R/W P10 1 1 to 3000 sec. 1
3357 NUM_3P R/W Unsi
ned Int 1 1 to 4 - 1
3358 3PDELAY1 R/W P10 1 1 to 3000 sec. 1
3359 3PDELAY2 R/W P10 1 1 to 3000 sec. 1
3360 3PDELAY3 R/W P10 1 1 to 3000 sec. 1
3361 3PDELAY4 R/W P10 1 1 to 3000 sec. 1
3362 RESETTIME R/W P10 1 1 to 3000 sec. 1
3363 DWELLTIME R/W P10 1 1 to 3000 sec. 1
3364 HOLD R/W Unsi
ned Int 1 0=No, 1=Yes - 0
3365 HOLDTIME R/W Unsi
ned Int 1 1 to 1000 sec. 1
3366 HOLDSENSE R/W Unsi
ned Int 1 0=CC, 1=CO - 0
Table B–4: MODBUS MEMORY MAP (Sheet 8 of 10)
ALPS
REGISTER
CONTENTS TYPE FORMAT NO. OF
REGS.
RANGE UNITS DEFAULT
1A 5A 1A 5A
1, 2, 3, 4, 5, 6, 7, 8
See pa
e B–14 for footnote explanations.