GE Power Management
ALPS Advanced Line Protection System B-13
APPENDIX B B.2 REGISTER MAPS
B
3367 SYNCHCHECK R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3368 CLOSEANG R/W P10 1 0 to 750 de
g
300
3369 SLIPFREQ R/W P10 1 1 to 50 Hz 10
3370 BUSLINE R/W Unsi
g
ned Int 1 0=BUS, 1=LINE - 1
3371 SYNCHPHASE R/W Unsi
g
ned Int 1 0=VA, 1=VB, 2=VC, 3=VAB,
4=VBC, 5=VCA
-0
3372 SYNCHHOLD R/W Unsi
g
ned Int 1 1 to 1000 sec. 1
3373 SP1PDELAY2 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3374 SP1PDELAY3 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3375 SP1PDELAY4 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3376 SP3PDELAY1 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3377 SP3PDELAY2 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3378 SP3PDELAY3 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3379 SP3PDELAY4 R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3380 SYNCMANCLS R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3381 VUBSLIVE R/W P10 1 1 to 1300 sec. 500
3382 VBUSDEAD R/W P10 1 1 to 1300 sec. 500
3383 VLINELIVE R/W P10 1 1 to 1300 sec. 500
3384 VLINEDEAD R/W P10 1 1 to 1300 sec. 500
3385 LBUSDLINE R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3386 DBUSLLINE R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3387 DBUSDLINE R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
3388 DELTAV R/W P10 1 1 to 300 V 100
3389 DELTAVBLK R/W Unsi
g
ned Int 1 0=No, 1=Yes - 0
PROTECTION SETTINGS: NON-CRITICAL ALARMS
3390 NCAIN1 R/W Unsi
g
ned Int 1 0 to 256 - 48
3391 NCAIN2 R/W Unsi
g
ned Int 1 0 to 256 - 49
3392 NCAIN3 R/W Unsi
g
ned Int 1 0 to 256 - 50
3393 NCAIN4 R/W Unsi
g
ned Int 1 0 to 256 - 51
3394 NCAIN5 R/W Unsi
g
ned Int 1 0 to 256 - - -
3395 NCAIN6 R/W Unsi
g
ned Int 1 0 to 256 - - -
3396 NCAIN7 R/W Unsi
g
ned Int 1 0 to 256 - - -
3397 NCAIN8 R/W Unsi
g
ned Int 1 0 to 256 - - -
PROTECTION SETTINGS: OUTPUTS
3398 T1 R/W Unsi
g
ned Int 1 0 to 256 - 33
3399 T2 R/W Unsi
g
ned Int 1 0 to 256 - 33
3400 T3 R/W Unsi
g
ned Int 1 0 to 256 - 33
3401 T4 R/W Unsi
g
ned Int 1 0 to 256 - 33
3402 T5 R/W Unsi
g
ned Int 1 0 to 256 - 34
3403 T6 R/W Unsi
g
ned Int 1 0 to 256 - 34
3404 A1 R/W Unsi
g
ned Int 1 0 to 256 - 58
3405 A2 R/W Unsi
g
ned Int 1 0 to 256 - 59
3406 A3 R/W Unsi
g
ned Int 1 0 to 256 - 33
3407 A4 R/W Unsi
g
ned Int 1 0 to 256 - 33
3408 A5 R/W Unsi
g
ned Int 1 0 to 256 - 37
3409 A6 R/W Unsi
g
ned Int 1 0 to 256 - 37
Table B–4: MODBUS MEMORY MAP (Sheet 9 of 10)
ALPS
REGISTER
CONTENTS TYPE FORMAT NO. OF
REGS.
RANGE UNITS DEFAULT
1A 5A 1A 5A
1, 2, 3, 4, 5, 6, 7, 8
See pa
g
e B–14 for footnote explanations.