EasyManua.ls Logo

GE L90

GE L90
900 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-56 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
FAULT LOCATOR CHAPTER 10: THEORY OF OPERATION
10
Figure 10-17: Relay connections for multi-ended fault locator example
The following settings are entered into the relays by you. These values are calculated in secondary ohms as shown in the
following tables.
Table 10-40: Line impedance settings (all angles are 80.5°)
Assume that the following signals are measured by the relays when the fault locator is triggered.
Table 10-41: Relay measurements (physical inputs)
These measurements are shown as follows in per-unit values of the CT and VT nominal of the 87L source.
Table 10-42: Relay measurements (per-unit values)
When subjected to the expanded Clarke transform in the previous section, the local currents yield the following values (in
relay per-unit values):
Relay 1: 1.3839 pu –84.504°
Relay 2: 5.4844 pu –85.236°
Relay 3: 1.2775 pu –56.917°
When subjected to the expanded Clarke transform in the previous section, the local voltages yield the following values (in
per-unit values of the nominal primary phase-to-ground voltage):
Value Relay 1 Relay 2 Relay 3
Local to tap 1.0219 sec. ohms (relay 1 to tap in
relay 1 secondary ohms)
6.0833 sec. ohms (relay 2 to tap in
relay 2 secondary ohms)
1.0707 sec. ohms (relay 3 to tap in
relay 3 secondary ohms)
Remote 1 to tap 1.7520 sec. ohms (relay 2 to tap in
relay 1 secondary ohms)
3.5483 sec. ohms (relay 1 to tap in
relay 2 secondary ohms)
1.3626 sec. ohms (relay 1 to tap in
relay 3 secondary ohms)
Remote 2 to tap 0.8030 sec. ohms (relay 3 to tap in
relay 1 secondary ohms)
2.7883 sec. ohms (relay 3 to tap in
relay 2 secondary ohms)
2.3360 sec. ohms (relay 2 to tap in
relay 3 secondary ohms)
Value Relay 1 Relay 2 Relay 3
F1 10.64 A –87.5° 8.592 A –88.5° 9.652 A –43°
F2 1.652 A 88.9° 1.273 A 78.6° 5.201 A –99°
F3 1.66 A –31.2° 1.614 A –43° 6.269 A 139.3°
F5 52.71 V 0.8° 76.943 V 24.579° 49.6 V 10.1°
F6 58.21 V –121.4° 86.321 V –98.052° 57.1 V –115.6°
F7 58.93 V 121.9° 78.795 V 137.27° 59.12 V 130.8°
Value Relay 1 Relay 2 Relay 3
IA 2.128 pu –87.5° 8.592 pu –88.5° 1.9304 pu –43°
IB 0.3304 pu 88.9° 1.273 pu 78.6° 1.0402 pu –99°
IC 0.332 pu –31.2° 1.614 pu –43° 1.2538 pu 139.3°
VA (VAB) 0.91304 pu 0.8° 0.92335 pu 24.579° 0.85917 pu 10.1°
VB (VBC) 1.0083 pu –121.4° 1.0359 pu –98.052° 0.98909 pu –115.6°
VC (VCA) 1.0208 pu 121.9° 0.94557 pu
137.27° 1.0241 pu 130.8°

Table of Contents

Related product manuals