GE Power Management LPS-O Line Protection Relay 12-
5
12 ASCII COMMUNICATIONS 12.1 INTRODUCTION
12
GROUP SETTING
The active Protectioning Setting Group number is 1
To select a Settin
Group enter Settin
Group
Number (‘1’ - ‘4’)
To select active settin
roup throu
h Contact
Converter Inputs enter ‘0’
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
Enter di
it from
0 to 4; enter
letter
INPuts Request contact converter
status
VIEW Contact Converter #0=0 (
SETTING GROUP BIT 0
)
Contact Converter #1=1 (
SETTING GROUP BIT 1
)
Contact Converter #2=1 (not assi
ned)
Contact Converter #3=0 (not assi
ned)
Contact Converter #4=0 (not assi
ned)
Contact Converter #5=1 (not assi
ned)
Contact Converter #6=0 (not assi
ned)
Contact Converter #7=1 (not assi
ned)
None
MODEL Retrieve the model
number, serial number,
and version of the relay
VIEW MODEL: LPSDA35U143VE3S
VERSION: V0001.11
None
CRCcalc Recalculates the CRC of
various settin
s
roups
(this is primarily a
troubleshootin
command
- it is used only where a
relay may have
one
throu
h a loss power
durin
a settin
s chan
e,
and the settin
s are
corrupted beyond the
ability of the relay to
correct).
SETTINGS CRCs are recalculated None
STLINID Allows the station and line
IDs to be chan
ed
SETTINGS Station ID: Current Station ID
Line ID: Current Line ID
Do you want to chan
e Station and/or
Line ID? (Y/N): y
Enter new Station ID (max. 32 characters): NEW
STATION ID
Enter new Line ID (max. 32 characters): NEW
FEEDER ID
Are you sure? (Y/N): y
Y to chan
e, N
to exit; NEW
STATION ID or
ENTER to keep
current ID; NEW
FEEDER ID or
ENTER to keep
current ID; enter
letter
Table 12–3: ASCII COMMAND LIST
(Sheet 4 of 7)
ASCII
Command
Mnemonic
Command Description Lowest
Level
Password
Needed
Relay Prompt User Response