GE Power Management LPS-O Line Protection System 2-
43
2 CALCULATION OF SETTINGS 2.5 REFERENCE TABLES
2
TABLE NOTES:
*
The IPB and IPT settings are fixed as shown and are NOT adjustable by the user.
Contact is normally open; add 1000 to number to close contact under normal conditions.
See Table 2–6 on page 2–33 for index assignments.
1621 KT1
(configurable)
KT1 Contact
0 to 256 step 1
0 to 256 step 1
0
1622 KT2
(configurable)
KT2 Contact
0 to 256 step 1
0 to 256 step 1
0
1623 KT3
(configurable)
KT3 Contact
0 to 256 step 1
0 to 256 step 1
0
1624 KT4
(configurable)
KT4 Contact
0 to 256 step 1
0 to 256 step 1
0
1625 CONFTRIP Initiate Three phase Trip with
Input from Xpression Builder
0 to 256 step 1
0 to 256 step 1
0
1626 CONFOSC Initiate Oscillography Capture
with Xpression Builder Input
0 to 256 step 1
0 to 256 step 1
0
Table 2–7: PROTECTION SETTINGS GUIDE (Sheet 7 of 7)
No.
Mnemonic
Description Range (5A) Range (1A) Default
see TABLE NOTES on page 2–43 for footnote explanation