G100 Instruction Manual
The DO operation types are PULSE, LATCH_ON and LATCH_OFF.
At runtime, commands received as CLOSE/ON are translated to LATCH_ON, and commands received
as TRIP/OFF are translated to LATCH_OFF. The PULSE command types are executed as PULSE,
according to their associated count and duration parameters
Analog DC Inputs (AI): 4
Each AI channel is configurable via internal jumpers as Full Scale either +5 VDC (Default setting) or 20 mA.
The resolution is 12-bit plus sign, self calibrating.
AI wiring is via a pluggable connector, pitch 3.5mm x 12 pins, located on the top side panel: