66 994-0155-1.00-1 GE Information
Appendix A – Standards &
Compliance
Compliance Standards
The G100 complies with the tests listed below.
Standard Description Test Level / Class
IEEE 1613
IEEE Standard Environmental and
Testing Requirements for
Communications Networking Devices
Installed in Electric Power Substations
Per standard
IEC 61850-3
Communication Networks and
systems for power Utility Automation-
Part 3
Per standard
IEC 62368-1
Audio/Video, Information And
Communication Technology
Equipment - Part 1: Safety
Per standard
IEC 60068-2-1 Cold -40
o
C for 16hours A
Cold start 1hour soak, 3 power ups every 10 mins A
IEC 60068-2-2 Dry Heat +70
o
C for 16hours A
Hot start 1hour soak, 3 power ups every 10 mins A
IEC 60068-2-78 Damp Heat, steady-state +40
o
C, 95%RH, non-condensing, 96hours A
IEC 60068-2-6
Vibration (sinusoidal)
0.5g, 1 sweep, 3 axes, with EUT energized
A
IEC 60255-21-1
1g, 10 sweep, 3 axes, with EUT non-
energized
IEC 60068-2-27
Shock Response
5g, 3 +/- shocks, 3 axes, with EUT
energized.
A
Shock Withstand
15g, 3 +/- shocks, 3 axes, with EUT non-
energized.
IEC 60068-2-27 Bump (Non-operating test)
10g, 1k bumps, 6 axes, with EUT non-
energized.
No damage,
functions
IEC 60068-2-31 Drop & Topple 100mm non-energized
No damage,
functions
IEC 60255-21-3 Seismic
1-35Hz; X axis: 7.5mm, 2g; Y axis: 3.5mm,
1g
A
EN 60255-27
Product safety requirements:
information technology equipment
Impulse: 1/5kV
PEAK
damage,
breakdown
or
Dielectric: 820V
RMS
/1150V
DC
Insulation Resistance: >100MΩ
CISPR22
Radiated Emissions: 30 MHz to 6 GHz
Class A
Conducted Emission NA