P74x/EN PL/N
1, P742, P743
(PL) 7-
Relay
English Text Type Source Description
PSL (50BF
Backtrip protection)
External Breaker failure trip order (50BF) of
zone 8 opto input
PSL (50BF
Backtrip protection)
External Breaker failure trip order (50BF) of
zone 1 opto input
Maintenance Mode 1 (87BB monitoring) of zone
8 opto input
Maintenance Mode 1 (87BB monitoring) of zone
1 opto input
Maintenance Mode 2 (50BF & 87BB blocked) of
zone 8 opto input
Maintenance Mode 2 (50BF & 87BB blocked) of
zone 1 opto input
Commissioning mode 1: 50BF disabled in zone
8
Commissioning mode 1: 50BF disabled in zone
1
Commissioning mode 2: 87BB & 50BF disabled
in zone 8
Commissioning mode 2: 87BB & 50BF disabled
in zone 1
Busbar trip order (87BB)
Logical OR of DDB 184 to 191
Locked
Busbar trip order blocked by commissioning
mode or Circuitry fault
Manual Trip Order Logical OR of DDB 192 to
199
Breaker fail trip order (50BF)
Logical OR of DDB 200 to 207
Breaker fail trip order blocked by commissioning
mode or Circuitry fault
50BF backtrip request by opto input
Logical OR of DDB 216 to 223
Differential fault current in phase A
Differential fault current in phase B
Differential fault current in phase C
Differential sensitive earth fault current
Circuitry fault Alarm on 1 or several zones
Logical OR of DDB 168 to 175
Commissioning mode 1: 87BB monitoring
Logical OR of DDB 224 to 231
Commissioning mode 2: 87BB & 50BF disabled
Logical OR of DDB 232 to 239
Valid Setting configuration
87BB alarm blocked by opto input (or between
the 8 inputs “INP block 3ph” z1 to z8)
Warning: fibre communication to be changed
Differential fault detected by the Check Zone
Circuitry fault in phase A
Circuitry fault in phase B
Circuitry fault in phase C
Circuitry fault on the neutral
Circuitry fault blocking Zone x
Logical OR of DDB 160 to 239
PU error Alarm in Zone x
Logical OR of DDB 152 to 159
PU error blocking Zone x
Logical OR of DDB 144 to 151
87BB SEF Busbar
Protection
87BB SEF blocked by opto input
Logical OR of DDB 208 to 215
Circuitry fault on the Check Zone
Circuitry fault blocking the Check Zone
PU error Alarm in the Check Zone