Technical Data
P74x/EN TD/N
a7
MiCOM P74
1, P742, P743 (TD) 2-
13
TD
COMMISSION TESTS
Monitor Bit 1(up to 8):
Binary function link strings, selecting which
DDB signals have their status visible in the
Commissioning menu, for test purposes
Test Mode: (CU)
Test Mode: Enabled or Out of Service
87BB trip blocked but 50BF (back trip)
enable per zone
87BB and 50BF trip blocked per zone
All the protections (87BB, Dead Zone,
General 50BF, Local 50BF, O/C) disabled
87BB disable but 50BF (back trip) enable
for all zones
Test Mode: (PU)
Test mode: Disabled / 50BF Disabled /
Overhaul
Test Pattern:
Configuration of which output contacts are
to be energised when the contact test is
applied.
Static Test Mode: Disabled/Enabled
Opto input voltage range:
24-27 V
30-34 V
48-54 V
110-125 V
220-250 V
Custom Opto Input 1
(up to # = max. opto no. fitted)
Custom options allow independent
thresholds to be set per opto, from the
same range as above
Filter Control:
Opto Input Labels
Opto Input 1 up to: 8 for P741
16 for P742
24 for P743
User defined text string to describe the
function of the particular opto input.
Outputs Labels
Relay 1 up to: 8 for P741 & P742
16 for P743
User defined text string to describe the
function of the particular relay output
contact.
IED CONFIGURATOR
Switch Conf.Bank:
No Action / Switch Banks
IEC61850 GOOSE
GoEna: Disabled/Enabled
Test Mode: Disabled / Enabled
VOP Test Pattern: 0x00000000 / 0xFFFFFFFF
Ignore Test Flag: No/Yes