P74x/EN PL/N
1, P742, P743
(PL) 7-
Relay
English Text Type Source Description
Triphase Circuit Breaker Trip from CU (Init
50BF TBF1 / TBF2), Logical OR of :
87BB, 50BF, Manual Trip Zone X
Phase A Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip A, External Trip
Phase B Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip B, External Trip
Phase C Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip C, External Trip
Indication of discrepancy between the 52a and
52b auxiliary contacts of the Circuit Breaker
Circuit Breaker Failed to Close
(after a manual/operator close command)
Circuit Breaker Failed to Trip
(after a manual/operator trip command)
Control Close in Progress
The relay has been given an instruction to close
the circuit breaker, but the Manual Close timer
Delay has not yet finished timing out
Control Close command to the circuit breaker.
Operates for a manual close command (menu,
SCADA)
Operator trip instruction to the circuit breaker,
via menu, or SCADA. (Does not operate for
protection element trips)
Any Trip (Logical OR of ddbs:
0, 1, 2, 168, 169, 170, 171, 256, 261)
All setting changes and most command/control
actions blocked for Rear Port 1.
All setting changes and most command/control
actions blocked for Rear Port 2 (not used).
87BB Phase Fault detected in phase A
87BB Phase Fault detected in phase B
87BB Phase Fault detected in phase C
87BB earth Fault detected
Assignment of signal to drive LED 1 Red.
Assignment of signal to drive LED 8 Red.
Input to Auxiliary Timer 1
Input to Auxiliary Timer 16
Output from Auxiliary Timer 1
Output from Auxiliary Timer 16
Trigger for the Fault Recorder
Front panel Battery Failure
48V Field Voltage Failure
This is an alarm that is ON if any setting fail
during the setting changing process. If this
happens, the relay will use the last known good
Phase A undercurrent CBF Dead Pole Start
Phase B undercurrent CBF Dead Pole Start
Phase C undercurrent CBF Dead Pole Start
Phase A overcurrent CBF Dead Pole Start