x/EN PL/Na7
7-
MiCOM P74
Relay
English Text Type Source Description
52-A (CB closed)
CB Auxiliary Input (phase A)
52-B (CB open)
CB Auxiliary Input (Phase A)
52-A (CB closed)
CB Auxiliary Input (phase B)
52-B (CB open)
CB Auxiliary Input (Phase B)
52-A (CB closed)
CB Auxiliary Input (phase C)
52-B (CB open)
CB Auxiliary Input (Phase C)
Circuit Breaker closed (not (CB Aux. (52b) AND
CB Aux. (52a)))
Circuit Breaker is not available to trip
Indication of discrepancy between the 52a and 52b
auxiliary contacts of the Circuit Breaker
CB status position forced open (by default) or
closed
Triphase Circuit Breaker Trip from CU (Init 50BF
TBF1 / TBF2), Logical OR of :
87BB, 50BF, Manual Trip Zone X
Phase A Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip A, External Trip 3ph
Phase B Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip B, External Trip 3ph
Phase C Circuit Breaker Trip (Init 50BF TBF3 /
TBF4), Logical OR of :
O/C Protection, External Trip C, External Trip 3ph
Circuit Breaker Healthy (Can Trip)
Backtrip triphase due to a trip initiation (at tBF4)
Phase A undercurrent CBF Dead Pole Start
Phase B undercurrent CBF Dead Pole Start
Phase C undercurrent CBF Dead Pole Start
Phase A overcurrent CBF Dead Pole Start
Phase B overcurrent CBF Dead Pole Start
Phase C overcurrent CBF Dead Pole Start
Neutral overcurrent CBF Dead Pole Start
Backtrip triphase due to a trip initiation from CU (at
tBF2)
Logical OR of ddb 121 and 270
Valid Setting configuration
Control Close command to the circuit breaker.
Operates for a manual close command (menu,
Control Input 1 - for SCADA and menu commands
into PSL
Control Input 32 - for SCADA and menu
commands into PSL
Operator trip instruction to the circuit breaker, via
menu, or SCADA. (Does not operate for protection
Manual closing order of the Circuit Breaker
Manual Trip Order of the Circuit Breaker
Control Close in Progress
The relay has been given an instruction to close
the circuit breaker, but the Manual Close timer
Delay has not yet finished timing out
Virtual Signal 01 from the CU to the PU via the
fibre optic
Virtual Signal 16 from the CU to the PU via the
fibre optic