102 ADV100 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.10.5 3328 Energysavetrqband2 perc FLOAT 10.0 0.0 100.0 ERWS _V_
This parameter is used to set a percentage used to calculate a range around the torque current the moment output
voltage reduction is aborted. The torque current is saved at the end of the voltage reduction phase. if the torque
current is not within the calculated range, due to a change in the load while functioning at low voltage, the output
voltage requested by the V/f curve must be restored.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.10.6 3340 Energysaveout FLOAT 16/32BIT 0.0 0.0 1.0 ER _V_
This parameter is used to read the request to reduce the output voltage.