ADV100 Functions description and parameters list 59
Vout output voltage on the card terminals.
StpVar actual value of the variable (variable unit)
SFVar full scale of the variable (variable unit)
Example of calculation of the AnalogoutXxscalefactor
To display the drive speed, use an analog instrument with eld of measurement from 0 ... 2V. This means that, to
display the speed of the drive, a voltage of 2V on the analog output of the drive must correspond to the maximum
speed. With a scale factor of 1 this would be 10V (Scale factor = 2V / 10 V = 0.200).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.5 1866 Analogout1Xmon cnt INT16 0 0 0 ER FVS
The actual value of the voltage present on analog output 1 of the expansion card is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.6 1868 Analogout2Xmon cnt INT16 0 0 0 ER FVS
The actual value of the voltage or current present on analog output 2 of the expansion card is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.7 1874 Anout1Xabsolute ENUM Disable 0 1 ERW FVS
15.8 1876 Anout2Xabsolute ENUM Disable 0 1 ERW FVS
Enables the relative analog output as an absolute value. If this parameter is set to 1 the voltage on the analog output
assumes the value of 0 - 10V regardless of the sign of the command signal.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.9 1882 Analogout1Xmin cnt INT16 -16384 -32768 +32767 ERW FVS
15.10 1884 Analogout1Xmax cnt INT16 16384 -32768 +32767 ERW FVS
Setting of the minimum and maximum values for the analog output for the voltage present on analog output 1 of the
expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.11 1890 Analogout2Xmin cnt INT16 -16384 -32768 +32767 ERW FVS
15.12 1892 Analogout2Xmax cnt INT16 16384 -32768 +32767 ERW FVS
Setting of the minimum and maximum values for the analog output in current or voltage present on analog output 2
of the expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.13 1898 Analogout2Xtype ENUM -10V..+10V 0 2 ERW FVS
Selection of the programmed signal on analog output 2 of the expansion card. Depending on the output signal, move
the switch on the regulation card. The standard output is coded for the signal in voltage.
0 -10V..+10V
1 0,20mA … 10V
2 4..20mA
Select option 0 in order to apply a maximum voltage of ±12.5V (typically ±10V/5mA) to analog output 2.
Select option 1 in order to apply a maximum voltage of +10V or a signal in current of 0 ... 20 mA to analog output 2.
The signal must be positive.
Select option 2 to apply a signal in current of 4...20 mA to analog output 2.

Table of Contents

Other manuals for gefran SIEIDrive ADV100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive ADV100 and is the answer not in the manual?

gefran SIEIDrive ADV100 Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive ADV100
CategoryController
LanguageEnglish

Related product manuals