ADV100 Functions description and parameters list 65
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.4 2106 Encoder1repetition ENUM No division 0 3 ERWZ FVS
Setting of the divider to apply to the encoder repetition output frequency.
0 No division
1 Divide 2
2 Divide 4
3 Divide 8
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.5 2108 Encoder1signalVpp V FLOAT 1.0 0.8 1.2 ERWZ FVS
Setting of the encoder signal peak-to-peak voltage value. Incremental sinusoidal encoders and absolute SinCos
encoders normally produce signals with a peak-to-peak voltage of 1 Vpp. Due to voltage drops along the cable, the
signal may have a lower peak-to-peak voltage when it reaches the feedback card, triggering the Speedfbkloss
alarm.
This parameter is used to congure the value of the peak-to-peak voltage of the incremental sinusoidal encoders
and absolute SinCos encoders on the input terminals of the feedback card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.6 2110 Encoder1signalcheck ENUM Check A-B 0 1 ERWZ FVS
Conguration of which channels of the incremental digital encoder must be controlled for processing the Speedfbk
loss[22].
0 Check disabled
1 Check A-B
2 Check A-B-Z
4 Check A-B-SE
If set to 1, the application checks for the presence of the signals of channels A-B
If set to 2, the application checks for the presence of the signals of channels A-B-Z
If set to 4, the application controls loss of feedback for SE (single ended) encoders.
If the application detects the absence of feedback the Speedfbkloss[22] is generated.
As loss of feedback cannot be detected at speeds of around zero, the control is only performed if the speed refer-
ence is higher than the value set in parameter 4564SpdFbkLossthreshold. It is also important to consider the fact
that when working with a speed reference slightly above the limit set in parameter 4564SpdFbkLossthreshold, the
speed error could exceed the set threshold, given the load or current limit, and generate false alarms.
In that case increase the value of parameter 4550SpdRefLossthreshold or of parameter 4554SpdRefLosshold-
off.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.7 2112 Encoder1SSIbits ENUM 25 13 25 ERWZ FVS
Setting of the length of the SSI package, dened as the number of clock cycles, as the absolute SSI encoders on the
market have package lengths varying from 13 to 25 bits.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.8 2130 Encoder1direction ENUM Not inverted 0 1 RWZ FVS
Selection of the encoder direction
0 Not inverted
1 Inverted
By setting 0 the encoder feedback signals are not inverted.
By setting 1 the encoder feedback signals are inverted.