CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022 80
System Troubles Register Map Modbus Communications
460012
0
GROUND FAULT LOOP 3
8
STYLE 6 NEG. LOOP 3
1
GROUND FAULT LOOP 4
9
STYLE 6 NEG. LOOP 4
2
GROUND FAULT LOOP 5
10
STYLE 6 NEG. LOOP 5
3
GROUND FAULT LOOP 6
11
STYLE 6 NEG. LOOP 6
4
GROUND FAULT LOOP 7
12
STYLE 6 NEG. LOOP 7
5
GROUND FAULT LOOP 8
13
STYLE 6 NEG. LOOP 8
6
GROUND FAULT LOOP 9
14
STYLE 6 NEG. LOOP 9
7
GROUND FAULT LOOP 10
15
STYLE 6 NEG. LOOP 10
460013
0
STYLE 6 POS. LOOP 3
8
PRINTER SUPERVISORY
1
STYLE 6 POS. LOOP 4
9
BUZZER SUPERVISORY
2
STYLE 6 POS. LOOP 5
10
CRT SUPERVISORY
3
STYLE 6 POS. LOOP 6
11
PRINT QUEUE FULL
4
STYLE 6 POS. LOOP 7
12
MEMORY LOSS
5
STYLE 6 POS. LOOP 8
13
PRINTER COVER OPEN
6
STYLE 6 POS. LOOP 9
14
PRINTER PAPER OUT
7
STYLE 6 POS. LOOP 10
15
PRINTER OFF LINE
460014
0
Workstation Fan Failure
8
STYLE 4 SHORT A LOOP 3
1
UPS Failure
9
STYLE 4 SHORT B LOOP 3
2
MANUAL MODE ENTERED
10
STYLE 4 SHORT A LOOP 4
3
NCM COMM LOSS
11
STYLE 4 SHORT B LOOP 4
4
STYLE 4 SHORT A LOOP 1
12
STYLE 4 SHORT A LOOP 5
5
STYLE 4 SHORT B LOOP 1
13
STYLE 4 SHORT B LOOP 5
6
STYLE 4 SHORT A LOOP 2
14
STYLE 4 SHORT A LOOP 6
7
STYLE 4 SHORT B LOOP 2
15
STYLE 4 SHORT B LOOP 6
460015
0
STYLE 4 SHORT A LOOP 7
8
GENERAL PS FAULT / POWER
SUPPLY TROUBLE
1
STYLE 4 SHORT B LOOP 7
9
STYLE 6 SHORT LOOP 1
2
STYLE 4 SHORT A LOOP 8
10
STYLE 6 SHORT LOOP 2
3
STYLE 4 SHORT B LOOP 8
11
STYLE 6 SHORT LOOP 3
4
STYLE 4 SHORT A LOOP 9
12
STYLE 6 SHORT LOOP 4
5
STYLE 4 SHORT B LOOP 9
13
STYLE 6 SHORT LOOP 5
6
STYLE 4 SHORT A LOOP 10
14
STYLE 6 SHORT LOOP 6
7
STYLE 4 SHORT B LOOP 10
15
STYLE 6 SHORT LOOP 7
460016
0 STYLE 6 SHORT LOOP 8 8 TM4 NO ANSWER
1 STYLE 6 SHORT LOOP 9 9 TM4 DISABLED
2 STYLE 6 SHORT LOOP 10 10 SELF TEST FAILED
3
NODE xxx COMMUNICATIONS
FAILURE
11 NETWORK INCOMPATIBILITY
4 NCM PIEZO BATTERY FAILURE 12 WORKSTATION FAILURE
5 DVC COMM LOSS 13 NETWORK MAPPING LIMIT EXCEEDED
6
POWER SUPPLY CABLE NOT
CONNECTED
14 INVALID NODE TYPE
7 TM4 TROUBLE 15 DISPLAY NODE LIMIT EXCEEDED
Table 7.33: System Troubles Register Map (Continued)