CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022 123
FireWarden Panels Connecting to the Panels
C.6.5 To Use Panel’s Printer Port Connection
Some FireWarden panels support data transfer through their printer terminal.
1. On the Gateway Side
Connect the serial cable into the RS-232 port of the gateway.
The RS-232 port is labeled as 6 in the Figure C.13.
2. On the Panel Side
Connect the serial cable in the DB9 serial port of the ANN-S/PG module on the panel.
3. Power Connection
On the Gateway Side
Connect to the 24V DC external power supply.
Switch the S7 Switch next to the RS-232 port towards NUP_OUT.
Figure C.12: The S7 Switch
On the Panel Side
Connect the power cable to a 24V DC external power source or the panel’s power
supply.
NOTE: Compatible CLSS Gateway firmware versions: 2.1.11.16 and above
!
CAUTION: ENSURE THAT ONLY THE ANN-S/PG IS CONNECTED AND NOT THE CLSS GATEWAY. ONLY
ONE OF THESE TWO CAN BE CONNECTED. BOTH OF THEM MUST NOT BE CONNECTED TOGETHER.