EasyManua.ls Logo

Honeywell HON-CGW-MBB

Honeywell HON-CGW-MBB
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLSS Gateway - Installation and Users’ Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022 107
Supported Panels Connecting to the Panels
C.2 Supported Panels
The CLSS Gateway supports the following panel variants:
AM Series Panels
ESSER Panels
Farenhyt Panels
FireWarden Panels
Gamewell-FCI Panels
Gent Panels
Morley-IAS Panels
NOTIFIER® UL
NOTIFIER® European Panels (EN)
Silent Knight Panels
Triga Panels
VESDA® Detectors
C.3 AM Series Panels
C.3.1 Connection Options
The gateway operates only with the AM Series fire alarm control panels listed in the table
below:
Table C.1: AM Series Panel Connection Options
Minimum Required Versions
For the Panel/CPU1: v1.0.703 | For SIB version Panel: v0.68
For the CLSS Gateway: 3.0.4.56
C.3.2 To Use an RS-232 Connection
Using an RS-232 cable the CLSS Gateway and the panel are connected.
The RS-232 port in the gateway board is labeled as 6 in the Figure C.2.
1. On the Gateway Side
Connect to an RS-232 port of the gateway board.
2. On the Panel Side
AM8200 Panels
AM8200 Panels
Connect the White wire to the RX pin of the SIB 8200 board.
Connect the Green wire to the GND pin of the SIB 8200 board.
Connect the Brown wire to the TX pin of the SIB 8200 board.
Fire Alarm Panel Models RS-485 UART/TTL RS-232 USB
AM8200
No No Yes
1
1 Use the SIB 8200 board
No
NOTE: The panel can be a stand alone panel or part of a network of panels.
NOTE: Because the SIB 8200 board on the panel connects to the gateway, the SIB board
cannot be used for printing the events.

Table of Contents

Related product manuals