108 NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Special Zone Outputs Presignal and Positive Alarm Sequence (PAS)
• TM-4 polarity reversal alarm output
• TM-4 municipal box output
• UDACT
Positive Alarm Sequence (PAS)
Outputs selected for PAS delay for 15 seconds. Acknowledgement within the 15-second delay will
set the Presignal Delay Timer to the full programmed value (60-180 seconds, including the PAS
delay of 15 seconds). When an alarm comes from an initiating device with a CBE list that includes
ZF0, the control panel delays the following outputs:
• System Alarm relay
• TM-4 polarity reversal alarm output
• TM-4 municipal box output
• UDACT