EasyManua.ls Logo

Honeywell SmartLine RMA800 - Page 135

Honeywell SmartLine RMA800
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 119
Hazardous Locations Certifications
MSG
CODE
AGENCY
TYPE OF PROTECTION
Electrical
Parameters
Ambient
Temperature
A
FM
Approvals
TM
(USA)
Explosion proof:
Class I, Division 1, Groups A, B, C, D; T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T4
Class 1, Zone 1, AEx d IIC T4 Gb
Class 2, Zone 21, AEx tb IIIC T 95
o
C IP 66 Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C,D, E,
F, G; T4
Class I Zone 0 AEx ia IIC T4 Ga
Note 2 -50 ºC to 70ºC
Non-Incendive
Class I, Division 2, Groups A, B, C, D; T4
Class I Zone 2 AEx nA IIC T4 Gc
Note 1 -50 ºC to 85ºC
Enclosure: Type 4X/ IP66/ IP67
ALL ALL
Standards: FM 3600:2018;FM 3611: 2018; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1:
2015; FM 3610: 2018; ANSI/ UL 60079-11: 2014; FM 3810: 2018; ANSI/ UL 60079-15:
2013; ANSI/ UL 60079-31 : 2015; FM Class 3615: 2018; FM 3616: 2011
B CSA-Canada
Explosion proof:
CSA 14.2689056
Class I, Division 1, Groups A, B, C, D;T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T4
Class I Zone 1 Ex db IIC T4 Gb
Ex db IIC T4 Gb
Zone 21 Ex tb IIIC T 95
o
C Db
Ex tb IIIC T 95
o
C Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
Intrinsically Safe:
CSA 14.2689056
Class I, II, III, Division 1, Groups A, B, C, D, E,
F, G; T4
Ex ia IIC T4 Ga
Note 2 -50
o
C to 70
o
C
Non-Incendive
CSA 14.2689056
Class I, Division 2, Groups A, B, C, D; T4
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Note 1 -50
o
C to 85
o
C
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL

Table of Contents