Page 120 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4
C ATEX
Flame-proof:
II 2 G Ex d IIC T4 Gb
II 2 D Ex tb IIIC T 95
o
C Db
Note 1 -20 ºC to 70ºC
Intrinsically Safe:
II 2 G Ex ia IIC T4 Ga
FISCO Field Device
Ex ia IIC T4
Note 2
-50
o
C to 70
o
C
Non-Incendive
II 3 G Ex nA IIC T4 Gc
Note 1 -50
o
C to 70
o
C
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
STANDARDS: EN 60079-0: 2012; EN 60079-1 : 2007; EN 60079-11 : 2011;
EN 60079-26 : 2006; EN 60079-31: 2009; EN 60079-15 : 2010;
IEC 60529 : 2009 with Corr 3
D IECEx
Flame-proof:
Ex d IIC T4 Gb
Ex tb IIIC T 95
o
C IP 66 Db
Note 1 -20 ºC to 70ºC
Intrinsically Safe:
Ex ia IIC T4 Ga
FISCO Field Device
Ex ia IIC T4
Note 2
-50
o
C to 70
o
C
Non-Incendive
Ex nA IIC T4 Gc
Note 1 -50
o
C to 70
o
C
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
STANDARDS: IEC 60079-0: 2011, Edition 6; IEC 60079-1 : 2007-04, Edition 6;
IEC 60079-11 : 2011, Edition 6; IEC 60079-15 : 2010, Edition 4
IEC 60079-26 : 2006, Edition 2; IEC 60079-31 : 2008, Edition 1,
IEC 60529 : 2009 with Corr 3
E SAEx
Flame-proof:
Ex db IIC T6..T5 Gb
Ex tb IIIC T 95
o
C Db
Note 1
T6: -20
o
C to 65
o
C
T95
o
C,
T5: -20
o
C to 85
o
C
Intrinsically Safe:
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
Note 2 -20
o
C to 70
o
C
Non-Incendive
Ex ec IIC T4 Gc
Note 1 --20
o
C to 85
o
C
Enclosure: IP66/ IP67
ALL
ALL
STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014;
IEC 60079-11: 2011; IEC 60079-7: 2006; IEC 60079-31: 2013
P CCoE/ PESO
Flame-proof:
Ex db IIC T6..T5 Gb
Note 1
T6: -20
o
C to 65
o
C
T5: -20
o
C to 85
o
C
Intrinsically Safe:
Ex ia IIC T4 Ga
Note 2 -20
o
C to 70
o
C
Enclosure: IP66/ IP67
ALL
ALL
STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014;
IEC 60079-11: 2011; IEC 60079-7: 2006; IEC 60079-31: 2013
Notes
1. Operating Parameters:
Voltage= 12 to 42 V Current= 25 mA
2. Intrinsically Safe Entity Parameters
For details see Control Drawing, 50089981.

Table of Contents

Other manuals for Honeywell SmartLine RMA800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell SmartLine RMA800 and is the answer not in the manual?

Honeywell SmartLine RMA800 Specifications

General IconGeneral
BrandHoneywell
ModelSmartLine RMA800
CategoryTouch Panel
LanguageEnglish

Related product manuals